TECHNICAL DATA
OUTSIDE DIAMETER OF ELECTRICAL CONDUIT/STEEL PIPE
EMT IMC RIGID/STEEL PIPE
SIZE
DECIMAL FRACTION DECIMAL FRACTION DECIMAL FRACTION
1/2 0.706 11/16 0.815 13/16 0.840 13/16
3/4 0.922 15/16 1.029 1 1.050 1-1/16
1 1.163 1-3/16 1.290 1-5/16 1.315 1-5/16
1-1/4 1.510 1-1/2 1.638 1-5/8 1.660 1-11/16
1-1/2 1.740 1-3/4 1.883 1-7/8 1.900 1-7/8
2 2.197 2-3/16 2.360 2-3/8 2.375 2-3/8
2-1/2 2.875 2-7/8 2.857 2-7/8 2.875 2-7/8
3 3.500 3-1/2 3.476 3-1/2 3.500 3-1/2
3-1/2 4.000 4 3.971 4 4.000 4
4 4.500 4-1/2 4.466 4-7/16 4.500 4-1/2
5 - - - - 5.563 5-9/16
OUTSIDE DIAMETER OF COPPER TUBE
MD TIP:
“Universal clamps can be used with both NOMINAL TYPE M, L, K
EMT and RIGID pipe SIZE DECIMAL FRACTION
- BUT - 1/4” 0.375 3/8
for the best possible fit, specify either EMT
or RIGID sizes.” 3/8” 0.500 1/2
1/2” 0.625 5/8
3/4” 0.875 7/8
1” 1.125 1-1/8
1-1/4” 1.375 1-3/8
1-1/2” 1.625 1-5/8
2” 2.125 2-1/8
2-1/2” 2.625 2-5/8
3” 3.125 3-1/8
3-1/2” 3.625 3-5/8
4” 4.125 4-1/8
5” 5.125 5-1/8
6” 6.125 6-1/8
8” 8.125 8-1/8